| HT1106XS |
HT1106XL |
HT1110XS |
HT1110XL |
| INPUT |
| Cold Start |
YES
Default output frequency will be 50Hz or settable |
| Acceptable Input Voltage |
110VAC~288VAC |
| |
100% load@>176VAC |
| 90% load@>154VAC |
| 75% load@>132VAC |
| 50% load@>110VAC |
| Phase |
Single phase in,single phase out |
| Transfer Voltage Range |
200VAC/208VAC(0.9), 220VAC/230VAC/240VAC(1) |
| -Line low transfer |
110VAC |
| -Line low recovery |
121VAC |
| -Line high transfer |
288VAC |
| -Line high recovery |
281VAC |
| Input Current |
| -Rating(nominal input voltage) |
30A/220V |
34A/220V |
49A/220V |
53A/220V |
| Input Power Factor |
≥0.99 |
| Input current distortion |
<4% |
| Input Frequency Range |
40~70Hz |
| OUTPUT |
| Frequency adaptable |
Settable |
| Power |
|
| -Power |
6KVA |
10KVA |
| -Power(kW) |
6KW |
10KW |
| Output Voltage |
|
| -Waveform(Bat. Mode) |
Pure Sine Wave |
| -Nominal voltage |
220VAC/230VAC/240VAC, 200VAC/208VAC(PF=0.9) |
| -Voltage regulation |
± 1 % |
| -Voltage distortion |
≤1% THD, linear load |
| ≤ 5% THD, non linear load |
| Output Frequency |
|
| -Synchronization range |
±5Hz default, settable |
| -Battery mode |
(50±0.1) Hz default |
| Transfer Time |
| -Line mode to battery mode |
0ms |
| -Inverter to bypass |
0ms |
| Efficiency |
| -Line mode with battery full charged |
94%@100% load, 94.5%@60% load |
94.6%@100% load, 95%@60% load |
| -ECO mode |
99.0% |
| Noise(1m away) |
<58dB |
| Overload Capability(Inverter) |
105% to 110% : Transfer to bypass after 10 mins. |
| 111% to 125% : Transfer to bypass after 1 mins. |
| 126% to 150%: Transfer to bypass after 30s |
| Overload Capability (Bypass Mode) |
less than 125%: long time running |
| 126% to 130% :Shutdown in 5 mins |
| 131% to 150% :Shutdown in 1 mins |
| > 150% :Shutdown in 200 ms |
| Crest Ratio |
3:1 |
| BATTERY |
| Rating/Type |
12VDC/7Ah |
Depend on the capacity of external batteries |
12VDC/9Ah |
Depend on the capacity of external batteries |
| Quantity |
16PCS default, 20PCS settable |
16-24PCS settable |
16PCS default, 20PCS settable |
16-24PCS settable |
| DC Voltage |
192VDC default, settable |
| Back-up Time |
3mins @5kW |
Depend on the capacity of external batteries |
2mins @8kW |
Depend on the capacity of external batteries |
| Charger |
| -Charging current (max) |
1A, settable |
5A max,settable |
1A,settable |
5A max,settable |
| -Float Charging Voltage |
2.25V/cell default, setttable via software |
| -Boost Charging Voltage |
2.25V/cell default, setttable via software |
| -Charging time |
8h recharge to 90% |
Depend on the capacity of external batteries |
8h recharge to 90% |
Depend on the capacity of external batteries |
| Leakage current |
<3mA |
| Indicator & Alarm |
| -Display |
LED+LCD |
| Inteface |
| -Smart RS232 |
Standard Cable support INVT Power Monitor Software |
| -EPO |
NC |
| -RS485(option) |
Installed in the intelligent slot |
| -SNMP(option) |
Power Managment from SNMP Manager and Web Browser |
| Option |
| -Intelligent Kits |
DB9 port, dry contact |
| -parallel |
4 units paralleled |
| -Super charger (12A) |
digitally controlled, 4-steps charge, settable |
| -USB |
B-type USB port |
| -SNMP Kits |
Pluggable type |
| Mechanical |
| -W*D*H (mm) |
190*426*705 |
190*426*336 |
190*485*705 |
190*485*336 |
| -Net Weight (KG) |
56 |
14 |
60 |
16 |
| -Package Weight (KG) |
60 |
16 |
65 |
18 |
| -Rack / Tower |
Tower |
| Color |
| |
|
|
|
|
| FUNCTION |
Compatible with half wave load |
|
| Main input breaker |
| Bypass input breaker |
| ECO mode |
| Battery cabinet |
| Self aging |
| Digital Charger |
| Remained Battery Capacity |