HT1106XS |
HT1106XL |
HT1110XS |
HT1110XL |
INPUT |
Cold Start |
YES
Default output frequency will be 50Hz or settable |
Acceptable Input Voltage |
110VAC~288VAC |
|
100% load@>176VAC |
90% load@>154VAC |
75% load@>132VAC |
50% load@>110VAC |
Phase |
Single phase in,single phase out |
Transfer Voltage Range |
200VAC/208VAC(0.9), 220VAC/230VAC/240VAC(1) |
-Line low transfer |
110VAC |
-Line low recovery |
121VAC |
-Line high transfer |
288VAC |
-Line high recovery |
281VAC |
Input Current |
-Rating(nominal input voltage) |
30A/220V |
34A/220V |
49A/220V |
53A/220V |
Input Power Factor |
≥0.99 |
Input current distortion |
<4% |
Input Frequency Range |
40~70Hz |
OUTPUT |
Frequency adaptable |
Settable |
Power |
|
-Power |
6KVA |
10KVA |
-Power(kW) |
6KW |
10KW |
Output Voltage |
|
-Waveform(Bat. Mode) |
Pure Sine Wave |
-Nominal voltage |
220VAC/230VAC/240VAC, 200VAC/208VAC(PF=0.9) |
-Voltage regulation |
± 1 % |
-Voltage distortion |
≤1% THD, linear load |
≤ 5% THD, non linear load |
Output Frequency |
|
-Synchronization range |
±5Hz default, settable |
-Battery mode |
(50±0.1) Hz default |
Transfer Time |
-Line mode to battery mode |
0ms |
-Inverter to bypass |
0ms |
Efficiency |
-Line mode with battery full charged |
94%@100% load, 94.5%@60% load |
94.6%@100% load, 95%@60% load |
-ECO mode |
99.0% |
Noise(1m away) |
<58dB |
Overload Capability(Inverter) |
105% to 110% : Transfer to bypass after 10 mins. |
111% to 125% : Transfer to bypass after 1 mins. |
126% to 150%: Transfer to bypass after 30s |
Overload Capability (Bypass Mode) |
less than 125%: long time running |
126% to 130% :Shutdown in 5 mins |
131% to 150% :Shutdown in 1 mins |
> 150% :Shutdown in 200 ms |
Crest Ratio |
3:1 |
BATTERY |
Rating/Type |
12VDC/7Ah |
Depend on the capacity of external batteries |
12VDC/9Ah |
Depend on the capacity of external batteries |
Quantity |
16PCS default, 20PCS settable |
16-24PCS settable |
16PCS default, 20PCS settable |
16-24PCS settable |
DC Voltage |
192VDC default, settable |
Back-up Time |
3mins @5kW |
Depend on the capacity of external batteries |
2mins @8kW |
Depend on the capacity of external batteries |
Charger |
-Charging current (max) |
1A, settable |
5A max,settable |
1A,settable |
5A max,settable |
-Float Charging Voltage |
2.25V/cell default, setttable via software |
-Boost Charging Voltage |
2.25V/cell default, setttable via software |
-Charging time |
8h recharge to 90% |
Depend on the capacity of external batteries |
8h recharge to 90% |
Depend on the capacity of external batteries |
Leakage current |
<3mA |
Indicator & Alarm |
-Display |
LED+LCD |
Inteface |
-Smart RS232 |
Standard Cable support INVT Power Monitor Software |
-EPO |
NC |
-RS485(option) |
Installed in the intelligent slot |
-SNMP(option) |
Power Managment from SNMP Manager and Web Browser |
Option |
-Intelligent Kits |
DB9 port, dry contact |
-parallel |
4 units paralleled |
-Super charger (12A) |
digitally controlled, 4-steps charge, settable |
-USB |
B-type USB port |
-SNMP Kits |
Pluggable type |
Mechanical |
-W*D*H (mm) |
190*426*705 |
190*426*336 |
190*485*705 |
190*485*336 |
-Net Weight (KG) |
56 |
14 |
60 |
16 |
-Package Weight (KG) |
60 |
16 |
65 |
18 |
-Rack / Tower |
Tower |
Color |
|
|
|
|
|
FUNCTION |
Compatible with half wave load |
|
Main input breaker |
Bypass input breaker |
ECO mode |
Battery cabinet |
Self aging |
Digital Charger |
Remained Battery Capacity |